Turbocor Chiller Liquid Level Valve Replacement

Turbocor Chiller Liquid Level Valve Replacement

Job Description:  Turbocor Chiller Liquid Level Valve Replacement

Area: Basingstoke

Issue Identified:  Following a recent attendance on site to investigate issues on a Turbocor Chiller our engineer advised that the liquid level valve had failed and required to be replaced.

Works carried out:

  • Decanted the Turbocor Chiller unit refrigerant into dedicated cylinders.
  • Weighed refrigerant for F gas records.
  • Removed and replaced the failed part LLV (liquid level valve)
  • Pressurised (pressure tested) the Turbocor Chiller with OFN (oxygen free nitrogen).
  • Once proved evacuated the system.
  • Reverted the charge of refrigerant to the Turbocor Chiller and commissioned.
  • Cleared site and completed all F Gas paperwork

ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996

Uniflair Chillers have a wide range of models with capabilities for sustainable refrigerant options. With non-ozone depleting refrigerant, excellent efficiency and powerful controls, these units are ideal for applications where temperature control is crucial. Uniflair Chillers have been designed to bring efficient, reliable cooling to all types of large commercial applications. ACES engineers are experts in service and maintenance of all Uniflair Chiller types. We have engineers based in London 24/7.

Some of the many Uniflair Chillers we support
  • Uniflair Aquaflair Chillers
  • Uniflair Air-Cooled Turbocor Chillers
  • Uniflair Intelligent Free-Cooling Chillers
  • Uniflair Adiabatic Chillers
  • Uniflair HFO R1234ze Chillers
  • Uniflair Dry Coolers
Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure, LLV – Liquid Level Valve