Turbocor Compressor Replacement on a Geoclima Chiller
Job Description: Turbocor Compressor Replacement on a Geoclima Chiller
Area: Historic England, Swindon
Issue Identified: Following a recent report investigation the Turbocor compressor had a critical failure fault and required replacement.

Works carried out:
- Isolated the Geoclima Chiller electrically and mechanically.
- Removed refrigerant into dedicated recovery cylinders for safe disposal.
- ACES lift and shift team removed Turbocor Compressor from bed.
- Replaced 2 condenser coils.
- ACES lift and shift team lifted new compressor into chiller bed.
- Pressure tested with OFN (oxygen free nitrogen) to locate any leaks.
- Once proved release OFN to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with virgin refrigerant.
- Test Ran and re-commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas certificate.