York Chiller 1, YASX0531, BEKM021926, Circuit 1 Compressor Replacement

York Chiller 1, YASX0531, BEKM021926, Circuit 1 Compressor Replacement

Works carried out:

  • Isolated the York Chiller unit electrically and mechanically.
  • Recovered refrigerant into certified cylinder for storage on site.
  • Weighed and confirmed the charge.
  • ACES Lift and Shift team removed compressor.
  • Replaced with a York Remanufactured Compressor by ACES.
  • Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and commissioned.
  • Completed waste transfer note and handed to on-site representative.
ACES maintain the cooling equipment of 10,000,000 sq. ft of retail buildings and offices in London, keeping over 200,000 people in a comfortable working environment.

We maintain, service and repair Chillers for most applications. The sectors we specialise in are Data Centres, Retail, Process and Commercial Buildings.

Data Centres rely on a constant temperature and it is extremely critical to maintain this. Over-heating or over-cooling can have dire consequences. ACES can detect any problematic hotspots.

Process and manufacturing sectors handle anything from food to chemicals and maintaining the temperature to a desired setting is crucial. Any breakdown can have a hefty financial impact on the business so having a planned preventative maintenance procedure in place is very important to reduce any unwanted downtime.

Commercial Buildings and Real Estate – whether it is a factory, hospital or hotel having somewhere warm or cool depending on the season is very important. We can upgrade your system to maintain temperatures for each department throughout each season.