York Chiller Compressor Replacement

Job Description: Compressor Replacement on York Chiller

Area: Mark Lane, London

Issue Identified: Following a maintenance visit to site our engineer found Chiller 2 circuit 1 did not operate due to faulty compressor A3. We advised this compressor to be replaced to bring Circuit 1 back into operation

York Chiller

Works carried out:

  • Isolated the York Chiller mechanically and electrically.
  • ACES Lift and shift team assisted with the installation and removal of the compressors.
  • Decommissioned and removed A3 compressor.
  • Installed new compressor.
  • Charged the system with oxygen free nitrogen (OFN) and pressure tested for 24hrs.
  • Once proved released (oxygen free nitrogen) OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Checked, charged and trim charged with virgin refrigerant.
  • Test ran and found a low suction alarm.
  • Fitted a new suction transducer cable and test ran.
  • Commissioned new compressor.
  • Completed all F Gas forms and waste transfer notes and handed to site representative.
  • Cleared site.