York Chiller Repairs System 1 and 2

York Chiller Repairs System 1 and 2

Job Description:  York Chiller Repairs System 1 and 2

Area: New Street Square, London

Issue Identified:  York Chillers: System 1 required replacement of oil level switch and system 2 required an overhaul to compressor.

Works carried out:

System 1

  • Isolated the York Chiller System 1 unit electrically and mechanically.
  • Recovered refrigerant into certified cylinder for storage on site.
  • Weighed and confirmed the charge.
  • Replaced the oil level switch.
  • Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.

System 2

  • Isolated the York Chiller System 2 unit electrically and mechanically.
  • Recovered refrigerant into certified cylinder for storage on site.
  • Weighed and confirmed the charge.
  • ACES lifting team attended site and removed the compressor.
  • Overhauled the compressor in our factory.
  • Lifting team re-attended and reinstated the compressor on the chiller bed.
  • Replaced compressor contactors.
  • Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.

ACES Group Can Also Supply and Install New York Chillers – Call Us On 01865 890996

Features and advantages of the York Chiller

The benefits of a York Chiller are reduced emissions, greater flexibility, more sustainable and better control. Designed for temperature sensitive operations such as data centres, manufacturing, and hospitals. ACES have a team of highly trained York specialist engineers. We offer a 24/7 service with most of our engineers based in London.

Some of the many York Chillers we support
  • YCAL Scroll Chiller
  • YLAA Scroll Chiller
  • YVAA Variable Speed Drive Screw Chiller
  • YVFA Free Cooling Variable Speed Screw Chiller
  • YCIV Variable Speed Drive Screw Chiller
  • YHAU-C Single Effect Steam Absorption Chiller
  • YHAU-CW Double Effect Steam Fired Absorption Chiller
  • YHAU-CG/CA-CXR Double Effect Direct Fired Chiller/Heaters
  • YHAU-CG/CA Double Effect Direct Fired Chiller/Heaters
  • YHAU-CL/CH Single Effect Hot Water Absorption Chiller
  • YHAP-C Absorption Heat Pump
  • YCUL Air-cooled Scroll Condensing Unit
  • YLUA Air-cooled Scroll Condensing Unit
  • YMC² Magnetic Bearing Centrifugal Chiller
  • YZ Magnetic Bearing Centrifugal Chiller
  • YK Centrifugal Chiller
  • YVWA Variable Speed Screw Chiller
  • YCWL Scroll Chiller
  • YK-EP Centrifugal Chiller With Economizer
  • YST Steam Turbine Centrifugal Chiller
  • Titan OM Custom Design Centrifugal Chiller
  • CYK Compound Centrifugal Chiller/Heat Pump
  • YD Dual Centrifugal Chiller
Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure